TMS International Tech(HK) Limited Hello! now TMS International Tech(HK) Limitedtms@lcdchip.com
Follow us :
Home > Blog > Blogs

Solid State Relay Selection Guide: Types, Sizing, and Replacements

2026/11/13 11:51:35

A solid state relay (SSR) uses a semiconductor output to switch a load in response to a control signal. To select one, match the relay to the load voltage and type, verify that your controller can drive the input, then check the continuous current at the actual enclosure temperature. A relay marked 25 A can have a much lower current limit when installed without the specified heat sink. OMRON SSR operating principles · OMRON G3NA ratings

solid state relay (SSR)

What Is a Solid State Relay and How Does It Work?

A solid state relay, sometimes called a semiconductor relay, performs the switching function of a relay without moving contacts. In a typical optically isolated SSR, the input signal drives an LED inside the relay. A light-sensitive circuit on the output side responds and controls a semiconductor switch, such as a TRIAC, a pair of SCRs or a MOSFET stage. The load draws its power from the load supply. The controller supplies the signal that commands the switch.

 Solid State Relay (SSR)

The lack of moving contacts makes SSRs useful for frequent switching and applications that need quiet operation. The output semiconductor dissipates heat while it conducts, and many SSRs pass a small leakage current in the off state. A mechanical relay may suit an infrequently switched load when low off-state leakage or low conduction loss matters. Compare both technologies under the actual load and duty cycle. OMRON SSR and mechanical relay comparison

AC vs DC Solid State Relays

Read the input and output ratings separately. A label such as 3–32 VDC input / 24–230 VAC output describes an SSR that accepts a DC control signal and switches an AC load. A 24 VDC PLC output can be compatible with the input of that relay, subject to the input current and switching thresholds. A 24 VDC solenoid needs an output explicitly rated for the DC load.

Which solid state relay output fits the load?
Load or application Output to evaluate What to check in the datasheet
Single-phase AC resistive heater Zero-cross AC SSR for on/off or time-proportional control AC voltage range, load current at enclosure temperature and heat sink requirements.
DC solenoid or valve DC-rated SSR, often with a MOSFET output Output polarity, steady current, turn-off transients and the recommended suppression method.
AC motor Motor-rated SSR or solid state contactor Motor rating, starting current and duration, starts per hour and overload protection.
Three-phase AC heater Solid state contactor intended for three-phase loads Line-to-line voltage, per-phase current, number of switched poles and mounting conditions.
Low-level signal or test channel PCB-mount photorelay with a suitable AC, DC or AC/DC output On-resistance, off-state leakage, output capacitance, switching time and pinout.

Standard TRIAC- and SCR-output AC relays rely on load current falling below the device's holding current before they stop conducting. A steady DC load may provide no such turn-off opportunity. For a DC circuit, use an SSR with an explicit DC output rating and check whether the output is polarity-sensitive. OMRON guidance on thyristor output behavior · Sensata AC motor selection guide

Zero-Cross vs Random Turn-On SSRs

A zero-cross SSR waits until the AC voltage across its output is near zero before it turns on. This can reduce switching noise on resistive loads. It is a common starting point for an AC heater controlled in bursts of complete cycles.

Zero-Cross vs Random Turn-On SSRs


A random turn-on SSR, also called an instant-on SSR, can begin conducting without waiting for a voltage zero crossing. It is used where the system needs to choose the firing point within the AC waveform, such as phase-angle control with a compatible controller. Motor and transformer applications need their own manufacturer guidance on switching mode and inrush.

For a typical TRIAC or SCR AC output, turn-on is governed by the trigger and the relay design, while turn-off depends on the load current. After the input signal is removed, the output normally continues to conduct until the current falls below its holding level near the next current zero crossing. With inductive loads, the voltage and current zero crossings can occur at different times. OMRON zero-cross explanation · OMRON explanation of SSR turn-off

How to Size a Solid State Relay for Your Load

1. Calculate the current and check the starting conditions

A 1,500 W, 120 VAC resistive heater draws approximately 12.5 A at its rated voltage, using 1,500 W ÷ 120 V. For this application, use 12.5 A as the nominal running current and check the load tolerance, supply range and any cold-start current. For motors, transformers and capacitive inputs, obtain the starting-current magnitude and duration from the load documentation. Compare them with the relay's surge rating at the stated pulse duration and repetition limits.

2. Read the current-versus-temperature curve

At 40°C ambient, OMRON lists a maximum load current of 25 A for the G3NA-225B-UTU with the specified heat sink arrangement and 4 A without a heat sink. The 12.5 A heater exceeds the no-heat-sink rating. With a heat sink, check the manufacturer's load-current-versus-ambient-temperature curve at the worst-case temperature around the SSR inside the cabinet. Verify that the curve covers the actual mounting orientation, spacing and cooling arrangement. OMRON G3NA load and heat sink ratings

3. Account for the heat released inside the enclosure

For an AC power SSR, a first-pass estimate can use the manufacturer's on-state voltage drop multiplied by the load current. Using 1.6 V × 12.5 A gives approximately 20 W of conduction loss while the heater is on. For a MOSFET-output SSR, use the manufacturer's loss data or estimate conduction loss from current squared times on-resistance at operating temperature. Use the exact part's thermal data and heat sink requirements to check the final design. OMRON G3NA on-state voltage drop · OMRON SSR heat dissipation guidance

4. Check off-state behavior and how the load will be disconnected

Off-state leakage can keep a sensitive input asserted or cause a low-power lamp to glow. Some AC SSRs also specify a minimum load current. Check both figures under the datasheet conditions. For equipment that must disconnect power after a fault, account for the possibility of an SSR failing with its output shorted. Provide an independent means of disconnecting the load, as required by the equipment design. OMRON guidance on off-state leakage · OMRON fail-safe design guidance

Panel-Mount SSRs vs PCB-Mount Photorelays

Panel-mount solid state relays are commonly used to switch power in control cabinets. Compare the output rating, terminal arrangement, heat sink, mounting dimensions and approvals. For a DIN-rail unit with an integrated heat sink, check the spacing and ambient temperature limits for the intended installation.

PCB-mount photorelays are often used to switch signals and smaller loads. For a high-impedance measurement channel, off-state leakage can affect accuracy. Output capacitance can couple fast-changing signals through an open channel, and on-resistance can affect the measurement while the channel is closed. Compare those parameters together with the input LED drive, isolation rating, package and pinout. Panasonic PhotoMOS and SSR selection guide

How to Find a Compatible Solid State Relay Replacement

Start with the manufacturer and the complete original part number, including the suffix. Pull both datasheets and compare their specifications under equivalent test and installation conditions. Two relays can have the same footprint and nominal current while requiring different input signals or cooling.

Solid state relay replacement checklist
Specification What to verify
Control input AC or DC, operating voltage range, required input current, on/off thresholds and polarity.
Output configuration AC, DC or AC/DC rating, operating voltage range, normally open or normally closed behavior and output polarity where applicable.
Switching behavior Zero-cross or random turn-on, turn-on and turn-off times, and compatibility with the controller's output timing.
Current and heat Continuous current at the actual ambient temperature, surge rating at the relevant duration, on-state loss and heat sink requirements.
Off-state performance Maximum leakage at the applicable voltage and temperature, minimum load current and output capacitance for signal applications.
Fit and compliance Mounting pattern or PCB footprint, terminal or pin assignment, clearance, isolation ratings and required approvals.

When sourcing an SSR, send the full part number and required quantity. If you need an alternative, include the control voltage, load type and voltage, running and starting current, mounting arrangement and any required approvals. If the part number is unreadable, include a clear photo of the label and terminal markings. Request a solid state relay quote

Frequently Asked Questions

What does 24 VDC mean on a solid state relay?

It can refer to the control input or the load output. If the marking reads 24 VDC input, check whether the controller can supply the required input current. For a 24 VDC load, look for an output voltage range that explicitly includes 24 VDC and verify the load current rating.

Can a 25 A SSR switch a 20 A load?

Compare 20 A with the allowable current at the actual operating temperature and with the installed heat sink. Check the load's starting current and duty cycle as well. The nominal 25 A rating is a starting point for looking up the relevant operating conditions.

Can I use a zero-cross SSR with PWM?

For an AC heater, a zero-cross SSR can work with a temperature controller that varies the proportion of complete AC cycles delivered to the load. High-frequency PWM for a DC load requires an output stage rated for the required switching frequency and associated power loss.

Why does a solid state relay appear to stay on after the input turns off?

A small current through a sensitive load can come from output leakage. An input that remains above the relay's release threshold can keep the output commanded on. A failed, shorted output is another possibility. The manufacturer's troubleshooting guide can help distinguish these cases by comparing the input state, load behavior and applicable specifications. OMRON SSR troubleshooting and failure modes

Can I use a general-purpose SSR for a motor?

Check for an explicit motor-load rating at the motor voltage and phase configuration. Match the motor's starting current and start duration, and check the controller's switching requirements. Motor overload protection is a separate function that needs to be covered by the motor control system. Sensata SSR and contactor selection for AC motors

What is the difference between a solid state relay and a solid state overload relay?

A solid state relay switches a load in response to a command. A solid state overload relay monitors motor current and issues a trip when its protection criteria are met. A motor control system may use both functions. Check the documentation for how the overload relay commands the motor switching device to open.

TMS International Tech(HK) Limited TMS International Tech(HK) Limited TMS International Tech(HK) Limited
TMS International Tech(HK) Limited
TMS International Tech(HK) Limited TMS International Tech(HK) Limited TMS International Tech(HK) Limited TMS International Tech(HK) Limited
Search

Search

PRODUCT

PRODUCT

PHONE

PHONE

USER

USER